Design of a square footing
The procedure for designing a square footing is as follows:
Service load design:
-
Determine
size of footing.
Reinforced concreter design:
-
Determine
depth of footing for punching shear and direct shear
-
Determine
footing reinforcement for bending moment.
-
Determine
column dowel to transfer column load.
Example: Design of a square footing
Given:
-
Column loads:
-
Live load: 80 kips
-
Dead load: 120 kips
-
Footing uplift: 0 kips
-
Column size: 1 ft. x 1 ft.
-
Soil information:
-
Allowable soil bearing capacity: 4000 psf
-
Soil cover above footing: 1 ft
-
Unit weight of soil: 120 pcf
-
Materials used:
-
Concrete strength at 28 day = 3000 psi
-
Yield strength of rebars = 60 ksi
Design code: ACI 318-05
Requirement: Determine
size, depth, and reinforcement for a square footing.
Solution:
Service load design:
1.
Determine footing sizes:
-
Assume a footing depth of 18”,net soil bearing capacity ,
-
Qnet
= 4000 – 150*18/12-120*1 = 3655 psf
-
Required footing are, A = (100+100) (1000) / 3655 = 54.7 ft2
-
Use 7'-6" by 7'-6" square footing. The footing
area is 56.3 ft2.
Reinforced concrete design:
2.
Determine footing depth
The factored footing pressure can be calculated as
Qu
= (1.2 x 120 + 1.6 x 80) / 56.3 = 4.83 psf
a. Check punching shear
-
Assume the reinforcements are #6 bars, the effective depth
-
d = 18" - 3" (cover) - 0.75" (one bar size)
= 14.3 " = 1.2'
-
The punch shear stress can be calculated as
-
vu =
4.83 [7.52-(1+1.2)2]*1000/[4 x 1.2 x (1+1.2) x 144] =
163.3 psi
-
The shear strength of concrete is
fvc
= 0.75 x 4 x (3000)1/2 = 164 psi O.K.
b. Check direct shear:
-
The distance from the critical section of direct shear to
the edge of the footing,
-
l =
7.5/2 -
1/2 – 1.2 = 2.05'
-
The direct shear stress is
-
vu
= (4.83)(1000)(2.05) / (12)(14.3) = 57.7 psi
per foot width of footing.
-
The shear strength of concrete for direct shear is
-
f
vc = 0.75 x 2 x
(3000)1/2 = 82
psi
> 57.7 psi
O.K.
3.
Determine footing reinforcement
-
The distance from face of column to the edge of the footing
is
-
l = 7.5/2 – 1/2
= 3.25'
-
The factored moment at the face of the column is
-
Mu
= (4.83)(3.25)2/2 = 25.5 k-ft. per foot width
of footing
-
Factor Rn
= (25.5)(1000)(12)/[(0.9)(12)(14.32)]=139.5 psi
-
Factor m =
60000/[(0.85)(3000)] = 23.5
-
The reinforcement ratio is
r
= (1/23.5){1-Ö[1-(2)(23.5)(139.5)/60000]} = 0.0024
-
Minimum reinforcement ratio,
r
= 0.0033 or r
= (4/3)*0.0024 =0.0032
-
As
= (0.0032 )(7.5)(12)(14.3) = 4.1 in2.
-
Use 10 - #6 bars in both directions, As = 4.4 in2.
4.
Designing column dowels:
-
The bearing capacity of concrete at column base is
-
Pc
= (0.65)(0.85)(3)(12)(12) = 238.7 kips
-
The factor column load is
-
Pu
= (1.2)(120)+ (1.6)(80) = 272 kips
-
The required area of column dowels is
-
As
= (272 - 238.7) / 60 = 0.56 in2
-
The minimum dowel area is
-
As,min
= (0.0005)(12)(12) = 0.72 in2
-
Use 4 - #4 dowels As
= 0.8 in2
-
The footing is shown in below

|