Wind load calculation ASCE 7-02
Method of wind calculation:
ASCE 7-02 provides two methods for wind load calculation: a
simplified procedure and an analytical procedure. The simplified procedure is
for building with simple diaphragm, roof slope less than 10 degree, mean roof
height less than 30 ft, regular shape rigid building, no expansion joints, flat
terrain and not subjected to special wind condition. The analytical procedure is for all buildings and
non-building structures. Each
procedure has two categories: wind for main wind force-resisting system and wind
for component and claddings.
Method 2: Analytical procedure
Apply to all buildings and other structures.
Velocity pressure:
Velocity pressure is calculated as
qz = 0.00256 Kz Kzt Kd V2
I (lb/ft2)
where
V is basic wind speed, I is important factor, Kd is wind
directionality factor, Kzt is topographic factor, and Kz
is velocity pressure exposure coefficient.
Velocity
pressure exposure factors are listed Table 6-3 of ASCE 7-02 or can be calculated
as
Kz = 2.01 (z/zg)2/a.
z
is height above ground, z shall not be less than 15 ft. except that z shall not
be less than 30 ft for exposure B for low rise building and for component and
cladding.
a
and zg are taken as follows:
|
Exposure
|
a
|
zg (ft)
|
|
B
|
7.0
|
1200
|
|
C
|
9.5
|
900
|
|
D
|
11.5
|
700
|
Topographic
Factor,
Kzt = (1+K1+K2+K3)2
where
K1, K2, K3 are determined from Figure 6-4 of
ASCE 7-02 based on hill, ridge or escarpment.
Wind load for main
wind force resisting system
Rigid building of all height:
The design wind pressure shall be calculated as
P = q G Cp – qi (GCpi)
Where
q = qz for
windward walls evaluated at height z above ground.
q = qh for
Leeward walls, side walls, and roof evaluated at mean roof height h above
ground.
G = 0.85 is gust response factor or may be calculated by Eq.
6-4.
Cp is external pressure coefficient from Figure
6.6 to 6.8 of ASCE 7-02.
-
Figure
6.6 is for gable, hip roof, monoslope roof, and mansard roof
-
Figure
6.7 is for dome roof
-
Figure
6.8 is for arched roof
GCpi is internal pressure coefficient from Figure
6.5 of ASCE 7-02.
qi is internal pressure evaluated as follows:
-
Enclosed
building: qi = qh evaluated at mean roof height for
windward, leeward, and side walls, and roof.
-
Partial
enclosed building: qi = qh for negative internal
pressure, qi = qz for positive internal pressure at
height z at the level of highest opening.
Note:
The internal pressure shall be applied simultaneously on windward and leeward
walls and both positive and negative pressures need to be considered.
Therefore, it cancels each other for enclosed building except for roof.
For partially enclosed building, internal pressure shall be added to
leeward wall at the height of opening.
Wall pressure coefficient Cp for Gable, Hip roof (from figure
6.6 of ASCE 7-02):
|
Surface
|
L/B
|
Cp
|
Use
with
|
|
Windward
Wall
|
All
values
|
0.8
|
qz
|
|
Leeward
Wall
|
0-1
|
-0.5
|
qh
|
|
2
|
-0.3
|
|
³
4
|
-0.2
|
|
Side
Wall
|
All
values
|
-0.7
|
qh
|
Low-rise building.
The design wind pressure shall be calculated as
P = qh[ (GCpf )– qi (GCpi)]
Where
qh is
velocity pressure at mean roof height h above ground.
GCpf is external pressure coefficient from Figure
6.10 of ASCE 7-02.
GCpi is internal pressure coefficient from Figure
6.5 of ASCE 7-02.
Note: For wind pressures at edges and corners of walls and
roof are higher than interior zone. Wind
pressure at each zone needs to be calculated seperatly.
External pressure coefficient GCpf (from Figure
6-10 of ASCE 7-02)
|
Roof
Angle
|
Building
Surface
|
|
1
|
2
|
3
|
4
|
5
|
6
|
1E
|
2E
|
3E
|
4E
|
|
0-5
|
0.4
|
-0.69
|
-0.37
|
-0.29
|
-0.45
|
-0.45
|
0.61
|
-1.07
|
-0.53
|
-0.43
|
|
20
|
0.53
|
-0.69
|
-0.48
|
-0.43
|
-0.45
|
-0.45
|
0.8
|
-1.07
|
-0.69
|
-0.64
|
|
30-45
|
0.56
|
0.21
|
-0.43
|
-0.37
|
-0.45
|
-0.45
|
0.69
|
0.27
|
-0.53
|
-0.48
|
|
90
|
0.56
|
0.56
|
-0.37
|
-0.37
|
-0.45
|
-0.45
|
0.69
|
0.69
|
-0.48
|
-0.48
|
Parapets
The design wind pressure shall be calculated as
Pp = qp GCpn
Where
qp is
velocity pressure at top of parapet.
GCpn is combined net pressure coefficient, +1.8
for windward, -1.1 for leeward.
Design wind load
with eccentricities
Wind
load design cases:
Case
1: Full wind loads in two perpendicular directions considered separately.
Case
2: 75% wind loads in two perpendicular directions with 15% eccentricity
considered separately.
Case
3: 75% wind loads in two perpendicular directions simultaneously.
Case
4: 56.3% (75%x75%) of wind load in two perpendicular directions with 15%
eccentricity simultaneously.
Wind load for component and cladding.
Building 60 ft or
lower
The design wind pressure shall be calculated as
P = qh[ (GCp )– qi (GCpi)]
Where
qh is
velocity pressure at mean roof height h above ground.
GCp is external pressure coefficient from Figure
6.11 to 6.16 of ASCE 7-02.
GCpi is internal pressure coefficient from Figure
6.5 of ASCE 7-02.
Building higher
than 60 ft
The design wind pressure shall be calculated as
P = q (GCp) – qi (GCpi)
Where
q = qz for
windward walls evaluated at height z above ground.
q = qh for
Leeward walls, side walls, and roof evaluated at mean roof height h above
ground.
qi is internal pressure evaluated as follows:
-
Enclosed
building: qi = qh evaluated at mean roof height for
windward, leeward, and side walls, and roof.
-
Partial
enclosed building: qi = qh for negative internal
pressure, qi = qz for positive internal pressure at
height z at the level of highest opening.
GCp is external pressure coefficient from Figure
6.11 to 6.17 of ASCE 7-02.
GCpi is internal pressure coefficient from Figure
6.5 of ASCE 7-02.
Note:
The internal pressure shall be applied simultaneously on windward and leeward
walls and both positive and negative pressures need to be considered.
Therefore, it cancels each other for enclosed building except for roof.
For partially enclosed building, internal pressure shall be added to
leeward wall at the height of opening.
Wind
pressure on parapets
The design wind pressure shall be calculated as
P = qp (GCp) – qi (GCpi)
Where
qp
= velocity pressure at top of parapets.
GCp is external pressure coefficient from Figure
6.11 to 6.17 of ASCE 7-02.
GCpi is internal pressure coefficient from Figure
6.5 based on porosity of the parapet envelope.
Wind
load on open building and other structures
The design wind load shall be calculated as
P = qz G Cf Af
Where
qz
= velocity pressure at height z at the centroid of Af.
G is gust effect factor.
Cf
is net pressure coefficients from Figure 6-18 to 6-22 of ASCE 7-02.
Af
is project area normal to the wind.
Example 3: Wind load on a billboard along highway.
Design Data:
Design code: ACE 7-02
Dimension of sign: 20 ft by 15
ft
Height from ground to center
of sign: 60 ft
Basic wind speed: 90 mph
Exposure category: B
Topographic feature: flat land
Requirement: Determine design
wind load on billboard to be used with load combination
Solution
1.Determine
basic wind speed from Figure 6.1 and directionality factor Kd from Table 6-6, V
= 90 mph, Kd = 0.85
2. Determine Important factor
from Table 6-1: I = 1
3. Determine Exposure category
from section 6.5.6 and velocity exposure coefficient Kz and Kh
from Table 6.5.
Exposure B, exposure
coefficient, a
= 9.5, zg = 900 ft
Height, z = 60 ft, Kz
= 2.01*(z/zg)2/a=
1.1
4. Determine topographic
factor from Figure 6.2, K1 = 0, K2 = 1, K3 = 1
Kzt = (1+K1K2K3)
= 1
5. Determine gust effect
factor from section 6.5.8, G = 0.85
6. Determine external pressure
coefficient Cf from Table 6-11
M = 20 ft, N = 15 ft, M/N =
1.3, Cf = 1.2
7. Determine velocity pressure
qz = 0.00256 KzKztKdV2I = 20.03 psf
8. Determine wind pressure: p
= qzGCf = 20.43 psf
9. Determine wind load on
billboard, F = pMN = 6130 lbs
|