One way slab design example

Example 1: Design of interior three span slab as shown below

Design code: ACI 318-05

Design data:

Number of span: 3

Length of spans: L1 = 20 ft, L2 = 24 ft, L3 = 20 ft

Thickness of slab: 6 in

Live load: WL = 50 psf

Superimposed dead load: WSD = 10 psf

Concrete compressive strength: fc' = 4000 psi

Yield strength of steel: fy = 60 ksi

Requirement: design slab reinforcement use ACI factors and check deflection

1. Check if two adjacent spans differ more than 20%.

    L2/L1 = 120%,     L2/L3 = 120 %        O.K.

Weight of slab: Ws = 75 psf

Total dead load: WD = 75 + 10 = 85 psf

Live load to dead load ratio: WL/WD = 0.6   < 3 O.K.

Calculate slab moments using ACI factors:

Assume 1 ft width of slab for calculation, b = 1 ft

Factored load: Wu = (1.2*85+1.6*50) * 1 = 182 lb/ft    (ACI 318-02, 05)

Positive moment:

Exterior span: Mu1 = 182*202 / 14 /1000 = 5.2 ft-kip

Interior span: Mu2 = 182*242 / 16 /1000 = 6.6 ft-kip

Negative moment:

Exterior face of first interior support: Mu3 = 182*202 / 10 /1000 = 7.3 ft-kip

Interior face of first interior support: Mu4 = 182*242 / 11 /1000 = 9.5 ft-kip

Interior face of Exterior support: Mu1 = 182*202 / 24 /1000 = 3.0 ft-kip

Design Positive moment reinforcement

Exterior span

Factored moment: Mu1 = 5.2 ft-kip

Concrete cover: 0.75"  for interior slab

Effective depth: d = 6 - 0.75-0.5 = 4.75 in

Factor: Rn = Mu1/(0.9 b d2 ) = 256.1 psi    m = fy/(0.85 fc') = 17.7

Reinforcement ratio, r = 1/m [ 1 - ( 1 - 2 m Rn / fy )]  = 0.00444

Area of reinforcement, As = r b d = 0.253 in2.

Use #5 at 12" O.C. area of reinforcement = 0.3 in2.

Interior span

Factored moment: Mu2 = 6.6 ft-kip

Factor: Rn = 322.7 psi    m = 17.7

Reinforcement ratio, r = 0.0057

Area of reinforcement, As = r b d = 0.323 in2.

Use #5 at 11" O.C. area of reinforcement = 0.327 in2.

Negative moment reinforcement

Design negative reinforcement for first interior support, 

Factored moment: Mu4 = 9.5 ft-kip

Factor: Rn = 469.3 psi    m = 17.7

Reinforcement ratio, r = 0.00845

Area of reinforcement, As = r b d = 0.482 in2.

Use #6 at 10" O.C. area of reinforcement = 0.528 in2.

Design negative reinforcement for Exterior support

Factored moment: Mu4 = 3.0 ft-kip

Factor: Rn = 149.4 psi    m = 17.7

Reinforcement ratio, r = 0.00255

Use minimum reinforcement, area of reinforcement, As = 1.33 r b d = 0.194 in2.

Use #4 at 12" O.C. area of reinforcement = 0.2 in2.

Temperature reinforcement: As = 0.0018*6*12 = 0.13 in2.

Use #4 at 18" O.C., area of reinforcement 0.133 in2.

Disclaimer:  The content of this website was obtained and edited from various resources.  The editor made reasonable effort of editing.  Nevertheless, the editor does not warrant, and assume no liability for accuracy and completeness of its content.  The viewer shall use his/her professional knowledge and judgment in use of the web content.        Webmaster: www.ce-ref.com